Permit: T16CM06432

Parcel: 115052420


Addresses:

244 W FLORES ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T16CM06432

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/05/2016 ELECTRIC - FINAL Approved
10/03/2016 ELECTRIC - FINAL Denied ground wires trimmed to fit into bround bar
panel box not secured to the wall
incorrect labeling on main panel and sub-panel
ground electrode is not secure to building.
09/12/2016 ELECTRIC - FINAL Denied 2 SUB PANELS-
WEST PANEL VIOLATIONS: GROUND IS NOT IN THE SAME CONDUIT AS FEEDER WIRES, LUGS ARE TOO SMALL FOR CONDUCTORS INSTALLED, BREAKERS 6&8 ARE NOT TIED TOGETHER (SINGLE POLE BREAKERS USED AS A TWO POLE), CONDUCTOR WIRE AT BREAKER 1 IS NOT INSTALLED PROPERLY, FEEDER CONDUIT IS NOT BONDED.

EAST PANEL VIOLATIONS: PANEL EXCEEDS THE MAXAMUM HEIGHT OF 6'6" TO TOP OF BREAKERS, GROUND WIRE RAN WITH FEEDERS IS TOO SMALL, SECONDARD GROUND IS TOO LARGE FOR THE LUG IT IS INSTALLED UNDER, TOP LEFT CONDUIT OF PANEL HAS 3 UNGROUNDED CONDUCTORS AND 2 GROUNDED CONDUCTORS- ID THE WIRES.
09/07/2016 ELECTRIC - FINAL Partial Approval AP TO PA TO ALLOW FOR R-1 INSPECTION

DAN INGRAM- 9/12/16: I DID NOT INPUT THIS INTO THE COMPUTER. THIS WAS CHANGED WITHOUT MY KNOWLEDGE.
09/06/2016 ELECTRIC - FINAL Not ready for Inspection