Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T16CM06432
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2016 | ELECTRIC - FINAL | Approved | ||
10/03/2016 | ELECTRIC - FINAL | Denied | ground wires trimmed to fit into bround bar panel box not secured to the wall incorrect labeling on main panel and sub-panel ground electrode is not secure to building. |
|
09/12/2016 | ELECTRIC - FINAL | Denied | 2 SUB PANELS- WEST PANEL VIOLATIONS: GROUND IS NOT IN THE SAME CONDUIT AS FEEDER WIRES, LUGS ARE TOO SMALL FOR CONDUCTORS INSTALLED, BREAKERS 6&8 ARE NOT TIED TOGETHER (SINGLE POLE BREAKERS USED AS A TWO POLE), CONDUCTOR WIRE AT BREAKER 1 IS NOT INSTALLED PROPERLY, FEEDER CONDUIT IS NOT BONDED. EAST PANEL VIOLATIONS: PANEL EXCEEDS THE MAXAMUM HEIGHT OF 6'6" TO TOP OF BREAKERS, GROUND WIRE RAN WITH FEEDERS IS TOO SMALL, SECONDARD GROUND IS TOO LARGE FOR THE LUG IT IS INSTALLED UNDER, TOP LEFT CONDUIT OF PANEL HAS 3 UNGROUNDED CONDUCTORS AND 2 GROUNDED CONDUCTORS- ID THE WIRES. |
|
09/07/2016 | ELECTRIC - FINAL | Partial Approval | AP TO PA TO ALLOW FOR R-1 INSPECTION DAN INGRAM- 9/12/16: I DID NOT INPUT THIS INTO THE COMPUTER. THIS WAS CHANGED WITHOUT MY KNOWLEDGE. |
|
09/06/2016 | ELECTRIC - FINAL | Not ready for Inspection |