Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T16CM06432
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2016 | ELECTRIC - SERVICE UPGRADE | Approved | ||
10/03/2016 | ELECTRIC - SERVICE UPGRADE | Denied | ground wires trimmed to fit into bround bar panel box not secured to the wall incorrect labeling on main panel and sub-panel ground electrode is not secure to building. |
|
09/07/2016 | ELECTRIC - SERVICE UPGRADE | Approved | ||
09/06/2016 | ELECTRIC - SERVICE UPGRADE | Denied | NO 2ND GROUND ROD, NO GAS BOND, NO ADDRESSING AT METER SOCKET, GROUNDS NEED TO BE IDENTIFIED IN PANEL, BREAKERS NEED TO BE LABELED, KO SEAL IS NOT NEMA 3R RATED. |