Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T16CM06405
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/24/2016 | PLUMBING - FINAL | Approved | ||
08/23/2016 | PLUMBING - FINAL | Denied | T&P NOT CONNECTED AND TERMINATED 6"-12" FROM PAN. DRAIN PAN NOT INSTALLED UNDER W/H. VENT NO CONNECTED AT TOP OF HEATER. NO DRIP LEG AT GAS CONNECT. CARBON MONOXIDE DETECTOR NEEDED. |