Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T16CM06361

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/26/2016 BUILDING - FINAL Approved IVRS - Inspection :*
10/19/2016 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999


*
10/19/2016 BUILDING - FINAL Denied PLANS CALL FOR #8 WIRE FROM INVERTER TO SERVICE PANEL, #10 WIRE INSTALLED
INVERTER SHOULD BE MODEL PV-6000-OUTD, MODEL PV-3.6-OUTD INSTALLED
PLANS CALL FOR 25 SOLAR PANELS, 17 PANELS INSTALLED
OWNER NAME IS CORRECT ON PLANS, INCORRECT ADDRESS