Permit: T16CM05776

Parcel: 133392530

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
08/24/2016 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
08/23/2016 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999

1- SHALL PROVIDE A SAFTEY PROTECTION PLATE THAT EXTENDS 2" BELOW THE TOP PLATE AT WAHER VENT.

2- SHALL PROVIDE A WATER TEST ON THE DWV SYSTEM TO THE TOP OF VENT.

2- SHALL PROVIDE A SEDIMENT TRAP AT THE WATER HEATER GAS SUPPLY.

4- SHALL REMOVE THE SANITARY TEE THAT IS POSITIONED ON ITS BACK FOR THE VENT TO THE WASHER BOX AND PROVIDE A DIRECTIONAL FITTING.


*
08/12/2016 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*