Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
09/12/2016 ELECTRIC - UFER Approved IVRS - Inspection :*
09/07/2016 ELECTRIC - UFER Not ready for Inspection 1- need bond bushing at main transformer
2-verify listing for 400a switch
3-label equipment disconnects
4-clean surfaces at grounding
5-ground conductor to gutter,not per plan and undersized, bond bushing jumper.