Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/12/2016 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |