Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T16CM05478

Parcel: 12009306A


Addresses:

702 E FAIR ST


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T16CM05478

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
09/12/2016 ELECTRIC - UFER Approved IVRS - Inspection :*
09/07/2016 ELECTRIC - UFER Not ready for Inspection 1- need bond bushing at main transformer
2-verify listing for 400a switch
3-label equipment disconnects
4-clean surfaces at grounding
5-ground conductor to gutter,not per plan and undersized, bond bushing jumper.