Permit: T16CM05329

Parcel: 133200940

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
09/01/2016 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
08/31/2016 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999

1- SHALL PROVIDE A SAN TEE FOR THE TRAP ARM TO THE BIDET. A COMBINATION TEE WYE IS NOT APPROVED TO BE LOCATED IN A VERTICAL POSITION TO SERVE A TRAP ARM. THIS WILL PLACE THE OUTLET OF THE VENT BELOW THE CROWN OF THE TRAP.

2- RETEST THE SYSTEM.


*
08/30/2016 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999

1- SHALL PROVIDE AN APPROVED COUPLING (ie MISSION COUPLING) WHERE THE NEW BLDG. DRAIN CONNECTS TO THE EXISTING BLDG. DRAIN. FERNCO COUPLINGS ARE APPROVED WITHIN THE STRUCTURE.

2- SHALL PROVIDE A VENT THAT RISES VERTICAL AT THE WATER CLOSET FOR THE WATER CLOSET.

3- SHALL PROVIDE A VENT THAT RISES VERICAL TO THE TRAP ARM FOR THE BIDET.

4- RE TEST THE DWV SYSTEM.




*