Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/23/2016 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/21/2016 | PLUMBING - INTERMEDIATE | Partial Approval | provide rev | |
| 10/19/2016 | PLUMBING - INTERMEDIATE | Denied | T&P may not terminate to sink tail piece. Provide an approved revision for location change and the use of PEX. Terminate TPR to an approved location, provide 18" of copper ahead of water heater. Complete work, correct trap arm slope. * |