Permit: T16CM05185

Parcel: 119042370


Addresses:

3444 S 9TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/11/2016 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/07/2016 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* Provide water bond, verify 2 ground rods, max # 14 wire on 15 amp breaker, address label, verify service lateral conductor size, Q: is this panel energized.