Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/03/2017 | ELECTRIC - INTERMEDIATE | Approved | ||
| 03/30/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | relocate smoke alarm or duct at top of stairs, maintain minimum 3' separation | |
| 03/10/2017 | ELECTRIC - INTERMEDIATE | Denied | MISSING FIRE CAULK AROUND ALL PLUMBING IN TOP PLATE. SECURE GAS PIPE IN SOUTWEST CORNER ROOM FIRE BLOCKING HAS BEEN REMOVED IN SOUTHWEST CORNER DRYER VENT HAS INCORRECT FIRE BLOCKING CAULK SECURE TOILET FLANGES GROUND ALL METAL ELECTRICAL BOXES BOND GAS PIPE MISSING CAULK IN SOME ON THE STUCCO PENETRATIONS. END INSPECTION |
|
| 02/02/2017 | ELECTRIC - INTERMEDIATE | Partial Approval | GROUND ALL METAL BOXES OUTSIDE THE HOME |