Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T16CM04860
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2016 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 11/07/2016 | BUILDING - FINAL | Denied | 1) MISSING BOND BUSHING IN DISCONNECT 2) MISSING 2ND METER BOX AND DISCONNECT ON PLANS 3) AT J-BOX, USED #10 WIRE, PLANS SHOW #8 WIRE. |
|
| 10/31/2016 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 NO WARNING LABELS ON CONDUIT FROM INVERTER TO ROOF. PROVIDE PHOTOS OF WARNING LABELS ON ROOF CONDUIT. INCORRECT BREAKER SIZE INCORRECT INVERTER INCORRECT SOALR PANELS ON ROOF. |
|
| 10/18/2016 | BUILDING - FINAL | Denied | IVRS - Inspection : There is no plan or job inspection card on site.| 925 * |