Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T16CM04724

Parcel: 13624450A

Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T16CM04724

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/06/2016 FIRE - KITCHEN EXH HOOD FINAL Approved
11/25/2016 FIRE - KITCHEN EXH HOOD FINAL Denied DENIED. RED TAGGED. STOP WORK ORDER ISSUED. WORK WO PERMITS. CEASE AND DESIST ALL HOOD WORK UNTIL PROPER PERMITS ARE OBTAINED AND LICENSED CONTRACTOR HIRED TO FINISH WORK.
1) Need separate permit for hood suppression system. Nonlicensed company/tech in the process of doing a UL 300 upgrade. Permit with drawings required.
2) New appliances/equipment under existing hood.
3) Nozzle change. Unknown if at correct height or correct nozzle.
4) Nozzles not aimed correctly.
5) Grease accumulation in cable conduit.
6) Need to verify links (temp/date).
7) Currently working on electrical for duct exhaust fans. They were blowing down and not up.
8) Need class k extinguisher mounted in kitchen.
9) ACCEPTANCE TEST REQUIRED.