Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T16CM04724
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2016 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
11/25/2016 | FIRE - KITCHEN EXH HOOD FINAL | Denied | DENIED. RED TAGGED. STOP WORK ORDER ISSUED. WORK WO PERMITS. CEASE AND DESIST ALL HOOD WORK UNTIL PROPER PERMITS ARE OBTAINED AND LICENSED CONTRACTOR HIRED TO FINISH WORK. 1) Need separate permit for hood suppression system. Nonlicensed company/tech in the process of doing a UL 300 upgrade. Permit with drawings required. 2) New appliances/equipment under existing hood. 3) Nozzle change. Unknown if at correct height or correct nozzle. 4) Nozzles not aimed correctly. 5) Grease accumulation in cable conduit. 6) Need to verify links (temp/date). 7) Currently working on electrical for duct exhaust fans. They were blowing down and not up. 8) Need class k extinguisher mounted in kitchen. 9) ACCEPTANCE TEST REQUIRED. |