Permit: T16CM04705

Parcel: 134263060


Addresses:

826 S LANGLEY AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
07/18/2016 PLUMBING - FINAL Approved IVRS - Inspection :*
06/22/2016 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999
1- SHALL PROVIDE A FULL SIZE T & P DRAIN, 1 INCH MINIMUM.
2- SHALL SEAL THE T & P WALL PENETRATION.
3- SHALL PROVIDE VERIFICATION OF THE EXPANSION TANK SIZE FOR THIS BOILER.
4- SHALL NOT PULD IN THE POWER CORDS INTO A POWER STRIP LOCATED ON THE FLOOR.


*