Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T16CM04683
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2018 | FIRE - FINAL | Approved | ||
05/03/2018 | FIRE - FINAL | Partial Approval | Fire alarm is completed. Fire sprinkler final is complete. OK for TCO until COFO. Emergency and Exit signs good. Fire Extinguishers good. Kitchen is closed and the fire system final will be 05-09-2018. Ok to occupy for this weekend. | |
05/02/2018 | FIRE - FINAL | Cancelled | IVRS - RI canceled | |
04/30/2018 | FIRE - FINAL | Not ready for Inspection | SITE NOT READY FOR INSPECTION. COMPLETE ALL EXITS, EMERGENCY LIGHTING, AND REMOVE ALL HAZARDS | |
04/25/2018 | FIRE - FINAL | Not ready for Inspection | Defered this to Glenn D'Auria. Gates are missing, hardware missing. Exit signs need to be adjusted, need proper address since they are a corner property. Fire alarm completed. Sprinklers still need the bells to be completed. Need to board up the open spaces. Need to add fire extinguishers. Property needs to have all fire finals ie: hoods and sprinklers completed prior to obtaining COFO and or TCO. |