Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/05/2016 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 07/14/2016 | ELECTRIC - SERVICE UPGRADE | Denied | ILLEGAL WIRE METHOD. SERVICE PANEL UPGRADE WITH NO PERTECTION, ILLEGAL WIRE SPLICE TO TEP SERVICE DROP, MISSING GROUND RODS, NO ADDRESS PLATE ON THE PANEL, PANEL MUST BE RELOCATED TO MEET TEP STANDARDS, "MAIN" BREAKER IS IN THE OFF POSITION AND THE HOUSE IS ENERGISED. OCCUPANT STATED THAT THE MECHANICAL SYSTEM WAS ALTERED 1 YEAR PRIOR, NO PERMIT ON RECORD. MUST ADD MECHANICAL INSPECTIONS TO PERMIT. |