Permit: T16CM04322

Parcel: 106070750


Addresses:

1319 W KLEINDALE RD


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T16CM04322

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
08/05/2016 ELECTRIC - SERVICE UPGRADE Approved
07/14/2016 ELECTRIC - SERVICE UPGRADE Denied ILLEGAL WIRE METHOD.
SERVICE PANEL UPGRADE WITH NO PERTECTION, ILLEGAL WIRE SPLICE TO TEP SERVICE DROP, MISSING GROUND RODS, NO ADDRESS PLATE ON THE PANEL, PANEL MUST BE RELOCATED TO MEET TEP STANDARDS, "MAIN" BREAKER IS IN THE OFF POSITION AND THE HOUSE IS ENERGISED.

OCCUPANT STATED THAT THE MECHANICAL SYSTEM WAS ALTERED 1 YEAR PRIOR, NO PERMIT ON RECORD. MUST ADD MECHANICAL INSPECTIONS TO PERMIT.