Permit: T16CM04296

Parcel: 13317062A

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T16CM04296

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/05/2016 BUILDING - FINAL Approved IVRS - Inspection :*
08/02/2016 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999
1- THE DETAIL FOR THE ELECTRIC WATER HEATER PL.0/201
CALL OUT FOR A DRIP PAN AND DRAIN.
2- THE FIXTURE SCHEDULE CALLS OUT FOR 17 GAGE TUBULAR P-TRAPS W/CO.
3- SHALL LABEL ALL CIRCUITS IN THE SERVICE PANEL DEAD FRONT.
4- THE ENTRY WAY HAS MORE THAN 1/4 INCH VERTICAL RISE AT THRESHOLD. REFERENCE 303.2 ICC A117.1 STANDARDS.
5- UNISEX TOILET ROOM IS IN WORKING ORDER. OKAY FOR TEMP C OF O.


*
08/01/2016 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
07/29/2016 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999
1- NOT READY FOR INSPECTION.


*