Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2016 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/18/2016 | ELECTRIC - FINAL | Denied | DEAD FRONT IS NOT UL LISTED AS A GE PANEL. 2 OPEN BREAKER SLOTS. (LIFE SAFETY) SELF TAPPER AT BOTTOM OF THE PANEL IS NOT LISTED TO HOLD IN THE UNLISTED DEADFRONT. |