Permit: T16CM03912

Parcel: 140150660


Addresses:

5512 S PINE WY

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/03/2016 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
07/11/2016 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999


*
07/11/2016 ELECTRIC - SERVICE UPGRADE Denied work not being done, another failed inspection will result in a re-fee
07/06/2016 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
07/06/2016 ELECTRIC - SERVICE UPGRADE Not ready for Inspection 1- provide address label at meter box, s.s. with embossed lettering
2-provide 2 ground rods with #4 ground wire
3-provide bonding to water line