Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2016 | FIRE - FINAL | Approved | will replace 2 missing escutcheons. will patch around 5 heads, entry, NW side. | |
| 11/01/2016 | FIRE - FINAL | Denied | 1) Need annual and 5yr sprink reports. 2) Need all ceiling tiles installed. Missing throughout. |
|
| 08/30/2016 | FIRE - FINAL | Partial Approval | 1. Okay for TCO of production area. | |
| 08/29/2016 | FIRE - FINAL | Denied | East Exit door swings inward Hardware on door requires a key lock installed too high on door Need emergency lights for common area and exit path. |
|
| 08/26/2016 | FIRE - FINAL | Denied | DENIED, NOT READY. Wanted a TCO. Some items to look at during final: -extinguishers -EM lighting -required exit signs -check door schedule for proper exiting, door swing, door hardware, etc... |