Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2016 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/22/2016 | ELECTRIC - FINAL | Denied | CONDUIT NOT SUPPORTED WITHIN 3' OF BOX. NO ADDRESS LABEL. 2ND METER PACK HAS OPEN/EXPOSED BUSSING. NO GROUND RODS ARE CLEARLY IDENTIFIED. SERVICE MAST IS NOT SUPPORTED. BREAKERS ARE NOT LABELED. |