Permit: T16CM03798

Parcel: 205940640

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T16CM03798

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/04/2016 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
08/02/2016 MECHANICAL - INTERMEDIATE Denied clr at b-vent, support gas pipe. perforated metal strapping and J hooks are not code approved.
dryer duct shall be mechanically fastened and sealed. IRC
M1502.4.2
flex duct supports not approved for lineset.

Lennar super John