Inspection History Details
Inspection Status: Partial Approval
Inspection History: BUILDING - FINAL
Permit Number - T16CM03742
Inspection Description - BUILDING - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/08/2018 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1- ROOM 209 LAVATORY COUNTER TOP SHALL BE 34 INCHES ABOVE FINISH FLOOR. 2- ROOM 209 REQUIRES A VERTICAL GRAB BAR AT THE WATER CLOSET. 3- SHALL CAULK THE WATER CLOSET IN ROOM 209. |
|
02/01/2018 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* | |
01/31/2018 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- GFCI RECEPTICALS ARE WIRED INCORRECTLY CHECK ALL UNITS. * |
|
01/23/2018 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* | |
01/19/2018 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1- 4TH FLOOR VISTA BLDG. FINAL IS OKAY EXCEPT UNITS 400,401 & 409. |
|
09/13/2017 | BUILDING - FINAL | Partial Approval | 1- BLDG. FINAL IS OKAY IN ROOMS 140,240,340,440 ONLY. 2- IN WALL DOMESTIC WATER DISTRIBUTION IN ROOM 120 AND 121 IS OKAY FOR SHEET ROCK. |
|
02/22/2017 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1- BLDG. FINAL IS OKAY FOR THE 2ND FLOOR ROOMS # 255 THRU 264 ONLY. 2- BLDG. FINAL IS OKAY FOR THE 1ST FLOOR ROOMS # 155 THRU 154 ONLY. |
|
02/16/2017 | BUILDING - FINAL | Partial Approval | 1- BLDG. FINAL IS OKAY FOR ROMMS #455 THRU 463. 2- BLDG. FINAL IS OKAY FOR ROOMS # 355 THRU 364. |
|
01/24/2017 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1- BLDG. FINAL IS OKAY FOR THE 3RD FLOOR ROOMS 341 THRU 354 ONLY. 2- 4TH FLOOR ROOMS 454 THRU 464 IS OKAY FOR SHEET ROCK. 3- 3RD FLOOR ROOMS 354 THRU 365 IS OKAY FOR SHEET ROCK. |
|
01/18/2017 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1- FIRST FLOOR FINAL IS OKAY FOR ROOMS #141 THRU #154. |
|
01/10/2017 | BUILDING - FINAL | Partial Approval | 1- BLDG. FINAL IS OKAY FOR THE 4TH FLOOR LEVEL ROOMS 441 THRU 454 EXCEPT ROOM #445. | |
01/05/2017 | BUILDING - FINAL | Partial Approval | 1- BLDG. FINAL IS OKAY FOR THE 2ND FLOOR ONLY. | |
01/05/2017 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1- BLDG. FINAL FOR ROOMS 4012 AND 409 ARE OKAY. |