Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T16CM03436

Parcel: 12410504A

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T16CM03436

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/28/2016 FIRE - FINAL Approved
12/16/2016 FIRE - FINAL Partial Approval TCO approved for full operation. Sprink and alarm have been finaled. Waiting on the following items to fully approve.
1) Need 5yr check valve inspection report.
2) Needs to add FACP sign to door.
3) Simplex needs to add suite # to address at central station.
12/14/2016 FIRE - FINAL Denied Still needs full fire final.
1. Fire Alarm Final needed for permit T16FC00047.
2. Need 5 year check valve inspection and report.
3. Add 704 Diamond to rear and front doors.
4. Add sign to rear door reading CAUTION OXIDIZING GAS(ES) STORED WITHIN NO SMOKING.
5. Operational permit needed for use of compressed gasses. (O2)
12/09/2016 FIRE - FINAL Denied Still needs full fire final. These are only notes from observations made while doing other inspections.
1) They were ordered to obtain an operations permit for compressed gasses (O2).
2) Label riser room door and FACP door if it needs it.
3) Still needs fire alarm final. t16fc00047, see notes.
4) Needs 5yr check valve inspection and report.
5) Add 704 diamond to rear and front doors.
6) Add following sign to rear door. CAUTION:
OXIDIZING GAS(ES) STORED WITHIN
NO SMOKING
7) Add O2 sign to closet doors containing o2 cylinders.