Date Description Inspector Results Comments
12/16/2016 MECHANICAL - FINAL Approved
12/14/2016 MECHANICAL - FINAL Partial Approval provide airbalance report
provide sterilization report
disconnect not in an approved location
ADA sinks too high
provide all certs and docs on med gas instalation
12/09/2016 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
11/16/2016 MECHANICAL - FINAL Denied MISSING FUSES IN DISCONNECT
PROTECT ABS PIPE FROM SUNLIGHT
EXHAUST VENTS MUST BE 10' FROM INLETS
END INSPECTION