Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - MD GAS/PRECONST MTG
Permit Number - T16CM03436
Inspection Description - PLUMBING - MD GAS/PRECONST MTG
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/16/2016 | PLUMBING - MD GAS/PRECONST MTG | Approved | ||
12/14/2016 | PLUMBING - MD GAS/PRECONST MTG | Partial Approval | provide airbalance report provide sterilization report disconnect not in an approved location ADA sinks too high provide all certs and docs on med gas instalation |
|
09/21/2016 | PLUMBING - MD GAS/PRECONST MTG | Denied | ON SITE WITH INSPECTOR B. BENEDON. THE MEDICAL GAS PIPING IS COMPLETE WITHOUT ANY PRYER INSPECTIONS. SEE THIRD PARTY REPORT FROM MEDICAL TECHNOLOGY ASSOCIATES. |