Permit: T16CM03436

Parcel: 12410504A

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T16CM03436

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/28/2016 BUILDING - FINAL Approved
12/16/2016 BUILDING - FINAL Partial Approval pending fire finals & sterilization report ,see C.O.T. B.O. for C.O.
note* drinking water provided at all water outlets, sinks/fountains tagged out "do not drink, under test" pendingsterilization approval, ok to set equipment
12/14/2016 BUILDING - FINAL Partial Approval provide airbalance report
provide sterilization report
disconnect not in an approved location
ADA sinks too high
provide all certs and docs on med gas instalation
all fire finals required, all other inspections approvedprior to final
12/09/2016 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*