Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T16CM03212
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/23/2016 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/17/2016 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
11/17/2016 | MECHANICAL - INTERMEDIATE | Partial Approval | 1- elec room open box's 2-pantry firewall no completed 3-smoke damper flange missing at return air 4- relocate duct smoke detector 5-nurse sta 206, open elec box's 6-police room cond. pipe runnung uphill, grid support wrong, damper flange not properly secured |
|
09/23/2016 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
09/02/2016 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
08/02/2016 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | repair torn line-set insulation in walls and above hard lids |