Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
Permit Number - T16CM03212
Inspection Description - BUILDING ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/23/2016 | BUILDING ABOVE CEILING | Approved | IVRS - Inspection :* | |
11/17/2016 | BUILDING ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
11/17/2016 | BUILDING ABOVE CEILING | Partial Approval | 1- elec room open box's 2-pantry firewall no completed 3-smoke damper flange missing at return air 4- relocate duct smoke detector 5-nurse sta 206, open elec box's 6-police room cond. pipe runnung uphill, grid support wrong, damper flange not properly secured |
|
11/10/2016 | BUILDING ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
11/03/2016 | BUILDING ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999 * |
|
10/25/2016 | BUILDING ABOVE CEILING | Partial Approval | south egress corr. ok | |
10/14/2016 | BUILDING ABOVE CEILING | Not ready for Inspection | complete fire cualk | |
09/29/2016 | BUILDING ABOVE CEILING | Partial Approval | B SIDE, COMPARTMENT A AND B OKAY TO CONCEAL. | |
09/23/2016 | BUILDING ABOVE CEILING | Partial Approval | IVRS - Inspection :* |