Inspection History: BUILDING - FINAL
Permit Number - T16CM03188
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/03/2016 | BUILDING - FINAL | Approved | ||
10/24/2016 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* | |
10/24/2016 | BUILDING - FINAL | Partial Approval | pending fire final | |
10/20/2016 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
10/20/2016 | BUILDING - FINAL | Not ready for Inspection | 1-paper towel dispenser too high (over 48") in restrooms 2-PVC on roof requires U.V. protection 3-lineset insulation requires U.V. protection 4-provide approved gasket at exhaust hoods, min. 1500 deg. 5-ABS on roof not to run exposed 6-restroom exhaust too close to OSA intake 7-all rooftop equipment requires labeling 8-left side hood failed smoke containment test 9-provide splatter shields at deep fryers 10-connect leashes to all rolling under hood kitchen equipment 11-wrap at grease duct not signed off, provide documentation of approval |