Permit: T16CM03188

Parcel: 129020510


Addresses:

2936 E BROADWAY BL


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T16CM03188

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/03/2016 BUILDING - FINAL Approved
10/24/2016 BUILDING - FINAL Partial Approval IVRS - Inspection :*
10/24/2016 BUILDING - FINAL Partial Approval pending fire final
10/20/2016 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
10/20/2016 BUILDING - FINAL Not ready for Inspection 1-paper towel dispenser too high (over 48") in restrooms
2-PVC on roof requires U.V. protection
3-lineset insulation requires U.V. protection
4-provide approved gasket at exhaust hoods, min. 1500 deg.
5-ABS on roof not to run exposed
6-restroom exhaust too close to OSA intake
7-all rooftop equipment requires labeling
8-left side hood failed smoke containment test
9-provide splatter shields at deep fryers
10-connect leashes to all rolling under hood kitchen equipment
11-wrap at grease duct not signed off, provide documentation of approval