Permit: T16CM03160

Parcel: 12701005D

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Date Description Inspector Results Comments
08/04/2016 PLUMBING - ABOVE CEILING Approved IVRS - Inspection :*
08/01/2016 PLUMBING - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999
1- SHALL CONNECT THE 2" NEW VENT TO THE EXSITING VTR.


*
07/28/2016 PLUMBING - ABOVE CEILING Partial Approval 1- AIR ADMITANCE VALVE SHALL NOT BE LOCATED IN THE PLENUM.
2- NOTE: SHALL PROVIDE A LETTER FROM THE ENGINEER FOR LOCATION OF AIR ADMITANCE VALVE.