Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T16CM02955
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/29/2017 | FIRE - ALARM FINAL | Approved | ||
03/23/2017 | FIRE - ALARM FINAL | Partial Approval | See notes on T16FC00290 | |
03/17/2017 | FIRE - ALARM FINAL | Partial Approval | Alarm permit T16FC00290 1) Need box around plug for communicator. 2) All games need to shut down on general alarm. Not just for suppression hood. All general alarms. All three hoods, smoke, pull, water flow. Relay for game shutdown malfunctioned (burned up) during testing. 3) Duct smokes not shutting down air handlers. 4) Need ROC/72 document. |