Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T16CM02955

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/29/2017 FIRE - ALARM FINAL Approved
03/23/2017 FIRE - ALARM FINAL Partial Approval See notes on T16FC00290
03/17/2017 FIRE - ALARM FINAL Partial Approval Alarm permit T16FC00290
1) Need box around plug for communicator.
2) All games need to shut down on general alarm. Not just for suppression hood. All general alarms. All three hoods, smoke, pull, water flow. Relay for game shutdown malfunctioned (burned up) during testing.
3) Duct smokes not shutting down air handlers.
4) Need ROC/72 document.