Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2016 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/26/2016 | MECHANICAL - INTERMEDIATE | Partial Approval | Relocate overflow sensors to main drain pan. Insulate suction line at fan coils. provide a stand pipe in condensate vent. All rooftop units ok. |