Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2016 | FRAMING | Approved | IVRS - Inspection :* | |
| 07/15/2016 | FRAMING | Not ready for Inspection | INSP CANCELLED SUPPORT FLEX DUCT. SUPPORT DRYER VENTS W/ APPROVED STRAPPING. RIVIT JOINTS. FLEX DUCT STRAPPING IS NOT APPROVED FOR LINE SET PIPING. SECURE AND SUPPORT PEX PER INSTALL INSTR. NOT TO EXCEED 32" OC ISOLATE PEX FROM GANG NAILERS SECURE FIRST FLOOR CLOSET FLANGES TO CONCRETE, WILL ALLOW CORROSION RESISTANT CONCRETE ANCHORS SECURE 2ND STORY CLOSET FLANGES WITH CORROSION RESISTANT SCREWS EQUALL TO BRASS. P2705.1 INSTALL AT FINISHED FLOOR ELEVATION OR PROVIDE INSTALLATION INSTRUCTIONS FOR INSPECTOR REVIEW. SUPPORT AND SECURE GAS PIPING AT FIRE PL AND OVERHEAD. PROVIDE A LATTER FOR FAU INSPT ABV CEILING. |