Permit: T16CM02480

Parcel: 12109006A


Addresses:

5151 E PIMA ST


Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Permit Number - T16CM02480

Inspection Description - PLUMBING - SEWER HCS CONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
12/15/2016 PLUMBING - SEWER HCS CONNECT Approved 1- 8" SEWER MAIN TAP APPROVED PER WASTE WATER MANAGEMENT FIELD INSPECTOR.
2- SEWER WATER TEST PROVIDED.
3- OKAY TO BACKFILL TRENCH.
4- AFTER HRS INSPECTION FEE PAID IN FULL.
12-13-16 165.00
12-15-16 165.00
12/07/2016 PLUMBING - SEWER HCS CONNECT Partial Approval 1- 6" SDR-35 SITE SEWER FROM MANHOLE #1 TO THE UPSTREAM CLEAN OUT IS OKAY, TRACER WIRE PROVIDED.
2- NOTE: SHALL PROVIDE AN AIR PRESSURE TEST AND MANDRELL PULL TEST TO PERFORMED AT A LATER TIME.