Permit: T16CM02480

Parcel: 12109006A


Addresses:

5151 E PIMA ST


Inspection Status: Approved

Inspection History: PLUMBING - MEDICAL GAS/TEST

Permit Number - T16CM02480

Inspection Description - PLUMBING - MEDICAL GAS/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
09/06/2017 PLUMBING - MEDICAL GAS/TEST Approved
06/30/2017 PLUMBING - MEDICAL GAS/TEST Partial Approval 1- AIR PRESSURE TEST PROVIDED.
2- THIS INSPECTION IS FOR THE MEDICAL GASY SYSTEM FROM NURSE STATION (C) TO THE MECHANICAL EQUIPMENT ROOM.
05/12/2017 PLUMBING - MEDICAL GAS/TEST Partial Approval 1- BLDG.C-3 CORRIDOR AND PATIENT ROOMS C-3 AND C-4 HVAC DUCT IS OKAY.
2- HVAC DUCT & FIREPLACE AND HIGH CEILING IS OKAY
3-GREASE HOOD EXHAUST DUCT INSTALLATION OKAY, SMOKE TEST TO BE PERFORMED AT A LATER TIME.
4- BLDG. C-3 AND C-4 ELECTRIC IN WALLS AND ABOVE CEILING IS OKAY.
5- MED GAS PRESSURE TEST PROVIDED. IN C-3 & C-4.
6- DWV WATER TEST PROVIDED IN C-3.
7- OVERHEAD AND IN WALL DOMESTIC WATER DISTRIBUTION IS OKAY IN C-3.
05/02/2017 PLUMBING - MEDICAL GAS/TEST Partial Approval MEDICAL GAS IN BLDG. (C) NORTH COORIDOR ONLY IS OKAY.
04/24/2017 PLUMBING - MEDICAL GAS/TEST Partial Approval 1- MEDICAL GAS PRESSURE TEST OF 150 PSI PROVIDED.
2- THIS INSPECTION IS FOR THE MED GAS SYSTEM LOCATED IN BLDG (C) 1 SOUTH ONLY AS NOTED ON PLAN.
04/11/2017 PLUMBING - MEDICAL GAS/TEST Partial Approval 1- 1/2" AND 3/4" OXYGEN SUPPLY TO ZVB LOCATED AT THE CORRIDOR WALL BY THE ELECTRICAL ROOM C 183 IS OKAY.
2- VERIFIED A 1/2" BRAZED FITTING AND T WAS AN EXCELLENT BURN.
3- THIS INSPECTIONS IS NOTED ON THE APPROVED PLANS.
03/28/2017 PLUMBING - MEDICAL GAS/TEST Partial Approval 1- VERIFICATION AND STORAGE OF MATERIALS FOR BLDG.(B) IS OKAY FOR INSTALLATION.