Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/06/2016 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/28/2016 | MECHANICAL - FINAL | Denied | IVRS - Inspection :23No Description.| 99946 Note; next fail or not ready = re-fee * |
|
| 04/26/2016 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* Provide correction notice from 4/4/16, provide GFCI @ unit receptacle, and provide neutral for receptacle, #12 wire @ rooftop receptacle not permitted on 50 amp breaker. | |
| 04/04/2016 | MECHANICAL - FINAL | Denied | IVRS - Inspection :23No Description.| 99946 * |