Permit: T16CM02308

Parcel: 138050170

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/13/2016 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/10/2016 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
05/04/2016 ELECTRIC - FINAL Denied IVRS - Inspection :23No Description.| 99946
*
04/25/2016 ELECTRIC - FINAL Denied NEXT DENIAL MAY RESULT IN REFEE
INSPECTION REPORTS TO BE AVAILABLE AT INSPECTION
1. SMOKE DETECTOR CIRCUIT 8 NOT HARD WIRED PER APPROVED PLAN
2. EXISTING CIRCUITS SHOW NEW WIRING THROUGHOUT
3. SERVICE PANEL PROVIDE CONTINUOUS #4 BARE FOR GROUND TO SECONDARY GROUND ROD
4. MIXED BRKR TYPES IN MAIN PANEL
5. EXPOSE ALL NEW MECHANICAL WORK FOR INSPECTION
6. PROVIDE SAFE ACCESS TO ROOF
7. ARC FAULT PER PLAN
STOPPED INSPECTION
IT APPEARS PLANS DO NOT MATCH SCOPE OF WORK.
EXPOSE ALL NEW WORK FOR INSPECTION
03/30/2016 ELECTRIC - FINAL Denied IVRS - Inspection :23No Description.| 99946
*