Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2016 | FIRE - FINAL | Approved | ||
| 05/26/2016 | FIRE - FINAL | Partial Approval | 1. Equipment must be lined up with existing hood suppression system nozzles. 2. remove dead bolt from the kitchen exit. 3. whos monitoring sprinkler system 4. domestic supply must be locked at valve 5. need 2 sidewall heads in head box. 6. need riser room sign on door to basement stairs and on wall at bottom of stairs with directional arrow 7. need em lights in basement hallways and stairs. 8. exit sign over WEst exit from dining must stay lit when power shut down. 9. remove one key lock cylinder from exit doors at front. may only have one with the appropriate sign over it. Other lock may be thumb turn. |
|
| 05/23/2016 | FIRE - FINAL | Prior to Final Inspectn | Existing outdated Kitchen sprinkler system must be tested and maintained in working condition or a permit shall be pulled to demo system. Anything that bears the 'appearance' of fire protection system shall operate as a fire protection system or be removed. |