Permit: T16CM02233

Parcel: 13316024L

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
07/13/2016 FIRE - FINAL Approved 1) need add head for coverage SE corner of building per marked plans
2) head taped
3) need to raise head for coverage over duct work
4) taped head
5) room has two heads that are 15 feet off the East wall
6) Insulation too low and touching a few uprights