Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T16CM02233

Parcel: 13316024L

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
07/14/2016 FIRE SPKLR - FINAL Approved
07/13/2016 FIRE SPKLR - FINAL Denied 1) need add head for coverage SE corner of building per marked plans
2) head taped
3) need to raise head for coverage over duct work
4) taped head
5) room has two heads that are 15 feet off the East wall
6) Insulation too low and touching a few uprights