Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T16CM02232
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/16/2016 | FRAMING | Approved | IVRS - Inspection :* | |
06/15/2016 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- PEX HOT AND COLD WATER LINES SHALL BE LOCATED A MINIMUM OF 12" FROM THE CAN LIGHTS IN THE ENTRY WAY AND FAMILY ROOM. 2- REAR PORCH CAN LIGHTS NOT LANDED. 3- GROUND TAG NOT CONNECTED ON LIGHT RECEPTICAL UNDER THE STAIRWELL. 4 STUCCO MESH INCOMPLETE. * |