Permit: T16CM02206

Parcel: 141361680

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T16CM02206

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/24/2016 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
06/22/2016 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999
1- SHALL LOCATE THE OUTLET OF THE VENT ABOVE THE CENTER LINE OF THE WASTE LINE FOR 2ND FLOOR WATER CLOSET.
2- SHALL PROVIDE SUPPORT EVERY 4'-0" ON ALL HORIZANTAL WASTE AND VENT LINES.
3- SHALL PROVIDE A MINIMUM OF 1" CLEARANCE FROM COMBUSTIONABLE MATERIALS FOR WATER HEATER B-VENT.



*