Permit: T16CM02135

Parcel: 12404100A


Addresses:

930 E 2ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
04/18/2019 ELECTRIC - SERVICE UPGRADE Approved Utility relocation.
- New service conductors from TEP Transformer.
- (6) sets of (4) #750 KCMIL / (1) #600 GRND / 4" Conduits.
- Existing SES (901-921) 2000A, 120/208V.
Verbal Clearance sent to TEP (INCR), Signature from Paul Carlisle for confirmation of payment from APA
04/15/2019 ELECTRIC - SERVICE UPGRADE Approved Sent verbal Clearance to TEP (RECN) for address 943 E. University.Utility relocation (3) new sets of (4) #600 Conductors, (1) #250 Grnd.
SES (943) ok to re-energize.
04/08/2019 ELECTRIC - SERVICE UPGRADE Approved Verbal Clearance sent (INCR).
Utility relocations Approved.
New conductors from new transformers to existing Gears Approved
$165 From IPA, Contractor confirmed payment with signature
Generator relocation/ New conductors Approved.
03/26/2019 ELECTRIC - SERVICE UPGRADE Denied Not complete
03/25/2019 ELECTRIC - SERVICE UPGRADE Not ready for Inspection Paul, Superintendent cancelled and recalled for tomorrow, Tuesday.