Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - PROGRESS
Permit Number - T16CM01914
Inspection Description - BUILDING - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/13/2018 | BUILDING - PROGRESS | Approved | ||
02/06/2018 | BUILDING - PROGRESS | Partial Approval | IVRS - Inspection :* 1- CLEAR GAS METER |
|
02/05/2018 | BUILDING - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- SHALL PROVIDE APPROVED GAS SHUT OFF VALVES AT THE METER MANAFOLD. AGA OR CSA VALVES ONLY. 2- RE TEST THE SYSTEM. * |
|
01/19/2018 | BUILDING - PROGRESS | Partial Approval | IVRS - Inspection :* | |
01/17/2018 | BUILDING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
01/12/2018 | BUILDING - PROGRESS | Partial Approval | IVRS - Inspection :* 1- FRAMING FOR THE 1ST FLOOR NORTH CHASE WALL IS OKAY FOR SHEET ROCK. |
|
03/01/2017 | BUILDING - PROGRESS | Partial Approval | IVRS - Inspection :* 1- THE CASSON BOLTS IMBED HAVE BEEN PROVIDED. |
|
02/27/2017 | BUILDING - PROGRESS | Partial Approval | IVRS - Inspection :* 1- STEEL REBAR FOR THE SOUTH EXTERIOR SLAB OF GRID LINE (E) IS OKAY FOR CONCRETE. |
|
08/23/2016 | BUILDING - PROGRESS | Partial Approval | IVRS - Inspection :* 1- ATTENDED A PRE CON MEETING WITH bfl SUPERINTENDENT ON FLOW OF THE INSPECTION REQUESTS. 2- SHALL PROVIDE A SEPARATE DEDICATED ADDRESS OS SUIT NUMBERS FOR THE NEW BUILDING. |