Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2016 | FIRE - FINAL | Approved | ||
| 05/31/2016 | FIRE - FINAL | Partial Approval | 1. Ok for TCO. 2. Tested all but the 2 horn/strobes and 1 smoke that needs to be added to the bathroom and vault. |
|
| 05/27/2016 | FIRE - FINAL | Denied | 1. Awaiting approved set of Fire Alarm Plans. 2. Need dedicated circuit for Fire Alarm. 3. Need to add flow switch to riser for Alarm. |
|
| 05/18/2016 | FIRE - FINAL | Denied | 1. Bolt needs to be removed from door #9. 2. Exit signs needed above door #9 and #23. 3. Panic bar needed per plans on door #27. |