Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T16CM01533
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/20/2022 | FIRE - FINAL | Approved | ||
07/07/2022 | FIRE - FINAL | Partial Approval | 1. Waiting for a report from pcwin report. | |
09/22/2021 | FIRE - FINAL | Partial Approval | Items needed for C of O -ERRC system installed and tested -Add access keys to commercial suites as TIs are completed. |
|
08/19/2021 | FIRE - FINAL | Partial Approval | OK to obtain TCO from the building department. Items needed for full CofO -Fire extinguishers need annual service -Horn/strobe device in north courtyard is full of water -ERRC needs to be installed and tested, it is under permit T21FC00570 |
|
06/28/2021 | FIRE - FINAL | Partial Approval | Items Needed: Fire Final: -Signage throughout, building address, stairwell signs, room & suite numbers. -3rd floor units 311 & 314 breaker panel not labeled Emergency lights: -Adjust lights to illuminate the ground -4th floor North corridor by elevator Exit signs: -2nd floor North stair hallway - chevron -2nd floor South stair hallway - chevron -1st floor south corridor end -1st floor north stairwell -2nd floor SE corridor -3rd floor NE corridor -3rd floor north stairwell -4th floor south & north stairway |