Permit: T16CM00728

Parcel: 106021540


Addresses:

224 W SMOOT DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/31/2020 ELECTRIC - FINAL Approved Ap
06/19/2019 ELECTRIC - FINAL Denied Submit as built to Plans or build to plan.
Revise electrical plan to match work done or build to plan. Missing smoke alarms. Arc fault protect per plan. Tamper resistant outlets per plan. Many added outlets and fixtures not to plan. Sub panel not on approved plans. Bathroom and closet not on approved plan. Bedroom windows do not meet emergency egress. Stopped inspection.
03/01/2019 ELECTRIC - FINAL Not ready for Inspection Work is incomplete