Permit: T16CM00701

Parcel: 110035860

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
12/28/2016 FIRE - FINAL Approved already approved by CB
11/04/2016 FIRE - FINAL Partial Approval TCO approved for occupancy. Fire watch established during business hours only until sprinkler monitoring installed and approved. Riowest assuming responsibility for fire watch.
1) Install lock box.
2) Need knox FDC caps.
3) Need alarm final.
4) Label riser room door, "riser room"
5) Label fire alarm door, "FACP"
6) Obtain proper permit for sprinkler monitoring. Do not install equipment without obtaining permit first.
7) Reinspection fee added. Must be paid before full approval.
11/03/2016 FIRE - FINAL Denied mount extinguishers.
order knox box.
install address numbers top corner of bldg.
install decal above main exit, "this door to remain unlocked while business is occupied"
need sprink and alarm final, see notes.