Permit: T16CM00407

Parcel: 136150190

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
04/08/2016 FIRE - FINAL Approved
04/01/2016 FIRE - FINAL Partial Approval Must pass Kitchen hood final first.
1) make up air did not go off
2) 3 ( 1 F rated nozzles were at 38 Inches. Min height from
appliance is 40 inches.

Passed all other portions of test - link test, pull station, exhaust remained on, gas valve shut off, all other nozzles are for the correct appliances and placed at the correct distances. arrangement matches plans.