Permit: T16BU01210

Parcel: 11108136A

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T16BU01210

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/06/2016 FIRE - ALARM FINAL Approved
09/28/2016 FIRE - ALARM FINAL Denied According to Scott with Central Alarm, the Firelite M4 alarm panel's 'board' was replaced by another vender after two attempts at a fire final. This other vender had tried to repair the board, but that had not been successful.
Central Alarm's permit is only for the installation of an external dialer. When testing the dialer installation, today, the panel sent an 'alarm' to the dialer when the sprinkler shut off valve was turned instead of a 'supervisory' The FACP read 'Z4' - alarm and sent the signal as an alarm to the dialer.
09/09/2016 FIRE - ALARM FINAL Denied Alarm wasn't ready to be tested. Existing FA panel was throwing trouble codes.
09/01/2016 FIRE - ALARM FINAL Denied 1. Alarm not reporting signals to the Central Station.