Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T16BU01210
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2016 | FIRE - ALARM FINAL | Approved | ||
09/28/2016 | FIRE - ALARM FINAL | Denied | According to Scott with Central Alarm, the Firelite M4 alarm panel's 'board' was replaced by another vender after two attempts at a fire final. This other vender had tried to repair the board, but that had not been successful. Central Alarm's permit is only for the installation of an external dialer. When testing the dialer installation, today, the panel sent an 'alarm' to the dialer when the sprinkler shut off valve was turned instead of a 'supervisory' The FACP read 'Z4' - alarm and sent the signal as an alarm to the dialer. |
|
09/09/2016 | FIRE - ALARM FINAL | Denied | Alarm wasn't ready to be tested. Existing FA panel was throwing trouble codes. | |
09/01/2016 | FIRE - ALARM FINAL | Denied | 1. Alarm not reporting signals to the Central Station. |